Number of exits required per story — SBC 201

Each story needs at least 2 exits for up to 500 occupants, 3 for 501 to 1,000, and 4 for more than 1,000 (SBC 201, clause 1006.3.3 and Table 1006.3.3). A single exit is allowed only in the cases of clause 1006.3.4.

Occupant load per storyMinimum number of exits or access to exits
1–5002
501–1,0003
More than 1,0004

The table applies to every story and every occupied roof. The required exits are separate and distinct, and their number is kept all the way to the exit discharge or a public way.

Clause 1006.3.4 allows a single exit from a story in set cases, among them: the occupant load and travel distance stay within Table 1006.3.4(1) or 1006.3.4(2); Groups R-3 and R-4; and parking garages where vehicles are mechanically parked.

An example from Table 1006.3.4(2): on the first story above or below grade plane, for Groups A, B, E, F, M and U, one exit is allowed where the occupant load is at most 49 and the exit access travel distance at most 23 m. That table does not allow a single exit on the third story above grade plane or higher. The table has footnotes that change some values, so read them.

The number of exits is not the whole answer: rooms and spaces within the story have their own rule in clause 1006.2.1.

Read clause 1006.3.3 in the code reader

General educational content (ref: SBC 201 §1006.3.3) — pending licensed-engineer review; not an official certification. Always rely on the official code text.